PARAMETER |
پارامتر |
عملکرد |
|---|---|
|
P0 - 02 : 1 |
Run |
|
P0 - 03 : 2 |
Analog Input |
|
P5 - 02 : 1 |
Fault Relay |
|
P0 - 17 : 3 - 5 second |
ACC |
|
P0 - 18 : 3 - 5 second |
DEC |
|
PP - 01 : 1 |
Factory Reset |
|
P0 - 10 : 50 Hz |
Frequency Max |
|
WIRING |
|
|---|---|
|
FORWARD → GND FORWARD → S1 |
FW |
|
AI1 → ( + ) GND → ( - ) |
Analog Input |
|
+24V → TA DRIVE FAULT → TC |
Fault Relay |
|
MODE3 |
|
|---|---|
|
P6 - 10 : 1 = Coast to stop |
Stop Mode |
|
PARAMETER |
پارامتر |
عملکرد |
|---|---|
|
1 : 01.02 |
Run |
|
01.03 : 2 |
Analog Input |
|
06.02 : 1 |
Fault Relay |
|
01.17 : 3 - 5 second |
ACC |
|
01.18 : 3 - 5 second |
DEC |
|
17.01 : 1 |
Factory Reset |
|
01.10 : 50 Hz |
Frequency Max |
|
WIRING |
|
|---|---|
|
FORWARD → DI1 FORWARD → COM |
FW |
|
AI1 → ( + ) GND → ( - ) |
Analog Input |
|
+24V → TC DRIVE FAULT → TA |
Fault Relay |
|
MODE3 |
|
|---|---|
|
07.10 : 1 = Coast to stop |
Stop Mode |
|
PARAMETER |
پارامتر |
عملکرد |
|---|---|
|
P0 - 02 : 1 |
Run |
|
P0 - 03 : 2 |
Analog Input |
|
P5 - 02 : 1 |
Fault Relay |
|
P0 - 17 : 3 - 5 second |
ACC |
|
P0 - 18 : 3 - 5 second |
DEC |
|
PP - 01 : 3 |
Factory Reset |
|
P0 - 10 : 50 Hz |
Frequency Max |
|
WIRING |
|
|---|---|
|
FORWARD → COM FORWARD → DI1 |
FW |
|
AI1 → ( + ) GND → ( - ) |
Analog Input |
|
+24V → T/A1 DRIVE FAULT → T/B1 |
Fault Relay |
|
MODE3 |
|
|---|---|
|
P6 - 10 : 1 = Coast to stop |
Stop Mode |
|
PARAMETER |
پارامتر |
عملکرد |
|---|---|
|
P0 - 02 : 1 |
Run |
|
P0 - 03 : 2 |
Analog Input |
|
P5 - 02 : 1 |
Fault Relay |
|
P0 - 17 : 3 - 5 second |
ACC |
|
P0 - 18 : 3 - 5 second |
DEC |
|
PP - 01 : 1 |
Factory Reset |
|
P0 - 10 : 50 Hz |
Frequency Max |
|
WIRING |
|
|---|---|
|
FORWARD → X1 FORWARD → COM |
FW |
|
AI1 → ( + ) GND → ( - ) |
Analog Input |
|
+24V → K1C DRIVE FAULT → K1A |
Fault Relay |
|
MODE3 |
|
|---|---|
|
P6 - 10 : 1 = Coast to stop |
Stop Mode |